Solar wire size chart
Find the copper cable size for a DC run in a van, RV or cabin solar system from its current and one-way length. Every size here comes from the same rule the Sunwire designer uses to label each wire.
Open the full-time camper van example in the designer
How Sunwire sizes a cable
The designer picks the smallest gauge that passes two tests:
- Heat: the cable's ampacity (the current it can carry) is at least 125% of the current in the run.
- Voltage drop: current × resistance × twice the one-way length (out and back) is no more than 3% of the system voltage.
Ampacities are for 105 °C insulated copper, single conductor in free air, from the ABYC E-11 table (outside engine spaces). Cables in the battery path (between the battery, its main fuse, the battery switch and the busbars) are also sized to carry at least the main fuse's rating.
12 V chart
Cable size in AWG by current and one-way length, at 12 V, for battery-side DC runs. Solar panel cable follows a stricter rule (below).
| Current | 3 ft | 5 ft | 10 ft | 15 ft | 20 ft | 25 ft |
|---|---|---|---|---|---|---|
| 10 A | 14 | 14 | 12 | 10 | 8 | 8 |
| 20 A | 14 | 12 | 8 | 6 | 6 | 4 |
| 30 A | 12 | 10 | 6 | 6 | 4 | 2 |
| 40 A | 10 | 8 | 6 | 4 | 2 | 2 |
| 50 A | 8 | 8 | 4 | 2 | 2 | 1 |
| 60 A | 8 | 6 | 4 | 2 | 1 | 1/0 |
| 80 A | 6 | 6 | 2 | 1 | 1/0 | 2/0 |
| 100 A | 4 | 4 | 2 | 1/0 | 2/0 | 3/0 |
| 150 A | 2 | 2 | 1/0 | 2/0 | 4/0 | over 4/0 |
| 200 A | 1/0 | 1/0 | 2/0 | 4/0 | over 4/0 | over 4/0 |
24 V chart
The same currents at 24 V. The heat test doesn't change, but each foot of cable can lose twice the volts before the drop reaches 3%, so long runs come down a size or more.
| Current | 3 ft | 5 ft | 10 ft | 15 ft | 20 ft | 25 ft |
|---|---|---|---|---|---|---|
| 10 A | 14 | 14 | 14 | 12 | 12 | 10 |
| 20 A | 14 | 14 | 12 | 10 | 8 | 8 |
| 30 A | 12 | 12 | 10 | 8 | 6 | 6 |
| 40 A | 10 | 10 | 8 | 6 | 6 | 4 |
| 50 A | 8 | 8 | 8 | 6 | 4 | 4 |
| 60 A | 8 | 8 | 6 | 6 | 4 | 2 |
| 80 A | 6 | 6 | 6 | 4 | 2 | 2 |
| 100 A | 4 | 4 | 4 | 2 | 2 | 1 |
| 150 A | 2 | 2 | 2 | 2 | 1/0 | 2/0 |
| 200 A | 1/0 | 1/0 | 1/0 | 1/0 | 2/0 | 3/0 |
"Over 4/0" means no single cable up to 4/0 AWG passes. The designer flags it and suggests a shorter run, parallel cables or a higher system voltage.
Ampacity and resistance by gauge
The designer's reference data: ampacity in free air, and resistance per 1,000 ft of copper.
| Gauge | Ampacity | Resistance per 1,000 ft |
|---|---|---|
| 14 AWG | 35 A | 2.525 Ω |
| 12 AWG | 45 A | 1.588 Ω |
| 10 AWG | 60 A | 0.999 Ω |
| 8 AWG | 80 A | 0.628 Ω |
| 6 AWG | 120 A | 0.395 Ω |
| 4 AWG | 160 A | 0.249 Ω |
| 2 AWG | 210 A | 0.156 Ω |
| 1 AWG | 245 A | 0.124 Ω |
| 1/0 AWG | 285 A | 0.098 Ω |
| 2/0 AWG | 330 A | 0.078 Ω |
| 3/0 AWG | 385 A | 0.062 Ω |
| 4/0 AWG | 445 A | 0.049 Ω |
Worked example: the full-time camper van
The cables in the full-time camper van example (12 V), as the designer sizes them:
| Run | One-way length | Current | Sized for | Cable | Voltage drop |
|---|---|---|---|---|---|
| Panel to PV breaker | 15 ft | 10.3 A | 16.1 A | 14 AWG | 1.26% |
| Charge controller to busbar | 4 ft | 60 A | 75 A | 8 AWG | 2.51% |
| Busbar to battery switch | 2 ft | 309.4 A | 400 A | 4/0 AWG | 0.51% |
| Busbar to inverter | 5 ft | 294.1 A | 367.6 A | 3/0 AWG | 1.52% |
| Busbar to fuse block | 4 ft | 15.3 A | 19.1 A | 14 AWG | 2.57% |
| Fuse block to fridge | 15 ft | 3.8 A | 4.7 A | 14 AWG | 2.37% |
Take the inverter cable. The 3,000 W inverter draws 3,000 ÷ (12 × 0.85) = 294.1 A, so the cable must carry 294.1 × 1.25 = 367.6 A. 2/0 AWG is rated 330 A, too little; 3/0 AWG is rated 385 A. Its drop over 5 ft is 294.1 A × 0.062 Ω ÷ 1,000 × 10 ft = 0.18 V, 1.52% of 12 V. Both tests pass, so it's 3/0 AWG.
Solar panel cable
Cable between the panels and the charge controller is sized for 156% of the panels' short-circuit current (NEC 690.8), and the drop is measured against the panels' working voltage instead of the battery's. In the full-time van, the panel run carries 10.3 A, is sized for 16.1 A at 62.2 V, and needs 14 AWG over 15 ft.
Quick answers
What size wire do I need for my solar system?
It depends on the current and the length of the run. Sunwire picks the smallest copper cable that carries 125% of the current and keeps the voltage drop under 3% over the round trip. For example, 100 A over 10 ft at 12 V needs 2 AWG; at 24 V it needs 4 AWG.
Why does a longer run need thicker wire?
Every foot of cable has resistance, so a longer run loses more voltage. Sunwire counts both the positive and negative cable (twice the one-way length) and moves up a size until the drop is under 3% of the system voltage. At 12 V and 40 A, 5 ft needs 8 AWG but 20 ft needs 2 AWG.
What size wire goes from solar panels to the charge controller?
Sunwire sizes solar panel cable for 156% of the panels' short-circuit current, per the electrical code (NEC 690.8), at the panels' working voltage. In the full-time van example that is 10.3 A × 1.5625 = 16.1 A, which needs 14 AWG for the 15 ft run.
Make it yours
In the designer every wire shows its gauge. Select a wire and set its one-way length in feet, and its gauge and the cable in the parts list update.
Open the full-time van in the designer See the full-time camper van example